SKU:

LC1D09B7TQ

Contactor, TeSys Deca, 3P(3 NO), AC-3/AC-3e, 0 to 440V, 9A, 24VAC 50/60Hz coil, bulk qty

$69.20
Available for Shipping : 24-Nov-2024
Contactor, TeSys Deca, 3P(3 NO), AC-3/AC-3e, 0 to 440V, 9A, 24VAC 50/60Hz coil, bulk qty
  • New modern look & feel of all machines
  • Designed to meet the requirements of Electro domestic and HVAC applications
  • Easier to install and operate with multi-standard screws
  • With IEC60335-1 compliance, improved fire resistance, and dustproof auxiliaries
  • Digital customer experience for technical documents
  • Maintenance guide via EcoStruxureTM Facility Expect
Manufacturer: Schneider Electric
TeSys D contactor, 3 poles (3NO), for motor control applications up to 9A/690V AC-3/3e (4kW@400V). It provides a 24V 50/60Hz AC coil, 1NO+1NC built-in auxiliary contacts (NC mirror certified), connection by screw clamp terminals. For operating rates until 3600 cycles/hour and environments until 60°C, it procures high reliability and durability. Compact (45mm width), DIN-rail mounting or screw fixing. Pack of 10 units. Multi standards certified (IEC, UL, CSA, CCC, EAC, Marine), Green Premium compliant (RoHS/REACh).

Products specifications

Attribute name Attribute value
Main
[Ie] rated operational current 9 A (at <60 °C) at <= 440 V AC AC-3e for power circuit, 25 A (at <60 °C) at <= 440 V AC AC-1 for power circuit, 9 A (at <60 °C) at <= 440 V AC AC-3 for power circuit
Utilisation category AC-3e, AC-1, AC-3
[Uc] control circuit voltage 24 V AC 50/60 Hz
Device short name LC1D
Range TeSys Deca, TeSys
Range of product TeSys Deca
Poles description 3P
Product or component type contactor
Contactor application resistive load, motor control
[Ue] rated operational voltage power circuit: <= 690 V AC 25...400 Hz
Complementary
Compatibility code LC1D
Associated fuse rating 25 A at <= 690 V coordination type 1 for power circuit, 20 A at <= 690 V coordination type 2 for power circuit, 10 A gG for control circuit conforming to IEC 60947-5-1
Control circuit type AC at 50/60 Hz
Protective cover with
[Ui] rated insulation voltage power circuit: 690 V conforming to IEC 60947-4-1, control circuit: 690 V conforming to IEC 60947-4-1, power circuit: 600 V UL certified, power circuit: 600 V CSA certified, control circuit: 600 V UL certified, control circuit: 600 V CSA certified
Overvoltage category III
Coil technology without built-in bidirectional peak limiting diode suppressor
Inrush power in VA 70-70 VA cos phi 0.75 (at 20 °C)
Auxiliary contact composition 1 NO + 1 NC
Average impedance 2.5 mOhm - Ith 25 A 50 Hz for power circuit
Power dissipation per pole 0.2 W AC-3e, 1.56 W AC-1, 0.2 W AC-3
Minimum switching current 5 mA for control circuit
Non-overlap time 1.5 ms on energisation between NC and NO contacts, 1.5 ms on de-energisation between NC and NO contacts
Heat dissipation 2-3 W at 50/60 Hz for control circuit
Mechanical durability 15000000 cycles
Tightening torque power circuit: 1.7 N.m - with screwdriver pozidriv No 2, control circuit: 1.7 N.m - with screwdriver pozidriv No 2, power circuit: 1.7 N.m - with screwdriver Philips No 2, power circuit: 1.7 N.m - with screwdriver flat Ø 6 mm, control circuit: 1.7 N.m - with screwdriver Philips No 2, control circuit: 1.7 N.m - with screwdriver flat Ø 6 mm
Minimum switching voltage 17 V for control circuit
Operating time 12...22 ms closing, 4...19 ms opening
Irms rated making capacity 250 A at 440 V for power circuit conforming to IEC 60947, 140 A AC for control circuit conforming to IEC 60947-5-1
Rated breaking capacity 250 kA at 440 V for power circuit conforming to IEC 60947
Safety reliability level B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1, B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1
Control circuit voltage limits 0.85...1.1 Uc (60-60 °C):operational AC 60 Hz, 0.8...1.1 Uc (60-60 °C):operational AC 50 Hz, 0.3...0.6 Uc (60-60 °C):drop-out AC 50/60 Hz
[Ith] conventional free air thermal current 25 A (at 60 °C) for power circuit, 10 A (at 60 °C) for control circuit
Motor power hp 2 hp at 200/208 V AC 50/60 Hz for 3 phases motors conforming to UL, 7.5 hp at 575/600 V AC 50/60 Hz for 3 phases motors conforming to UL, 7.5 hp at 575/600 V AC 50/60 Hz for 3 phases motors conforming to CSA, 5 hp at 460/480 V AC 50/60 Hz for 3 phases motors conforming to UL, 5 hp at 460/480 V AC 50/60 Hz for 3 phases motors conforming to CSA, 2 hp at 230/240 V AC 50/60 Hz for 3 phases motors conforming to UL, 2 hp at 230/240 V AC 50/60 Hz for 3 phases motors conforming to CSA, 2 hp at 200/208 V AC 50/60 Hz for 3 phases motors conforming to CSA, 1 hp at 230/240 V AC 60 Hz for 1 phase motors conforming to UL, 1 hp at 230/240 V AC 60 Hz for 1 phase motors conforming to CSA, 0.5 hp at 115 V AC 60 Hz for 1 phase motors conforming to UL, 0.5 hp at 115 V AC 60 Hz for 1 phase motors conforming to CSA
Motor power kW 2.2 kW at 400 V AC (AC-4), 2.2 kW at 220...230 V AC 50/60 Hz, 4 kW at 415...440 V AC 50/60 Hz, 5.5 kW at 660...690 V AC 50/60 Hz, 5.5 kW at 500 V AC 50/60 Hz, 4 kW at 380...400 V AC 50/60 Hz
Hold-in power consumption in VA 7-7 VA 50/60 Hz cos phi 0.3 (at 20 °C)
Maximum operating rate 3600 cyc/h 60 °C
Connections - terminals power circuit: screw clamp terminal 2 1-2.5 mm² - cable stiffness: flexible with cable end, power circuit: screw clamp terminal 1 1-4 mm² - cable stiffness: flexible with cable end, power circuit: screw clamp terminal 2 1-4 mm² - cable stiffness: flexible without cable end, power circuit: screw clamp terminal 1 1-4 mm² - cable stiffness: flexible without cable end, power circuit: screw clamp terminal 2 1-4 mm² - cable stiffness: solid without cable end, power circuit: screw clamp terminal 1 1-4 mm² - cable stiffness: solid without cable end, control circuit: screw clamp terminal 2 1-2.5 mm² - cable stiffness: flexible with cable end, control circuit: screw clamp terminal 1 1-4 mm² - cable stiffness: flexible with cable end, control circuit: screw clamp terminal 1 1-4 mm² - cable stiffness: flexible without cable end, control circuit: screw clamp terminal 2 1-4 mm² - cable stiffness: solid without cable end, control circuit: screw clamp terminal 2 1-4 mm² - cable stiffness: flexible without cable end, control circuit: screw clamp terminal 1 1-4 mm² - cable stiffness: solid without cable end
Pole contact composition 3 NO
[Uimp] rated impulse withstand voltage 6 kV conforming to IEC 60947
Insulation resistance > 10 MOhm for control circuit
Mounting support rail, plate
Environment
Fire resistance 850 °C conforming to IEC 60695-2-1
Quantity per set set of 10
Mechanical robustness vibrations contactor closed (4 Gn, 5...300 Hz) , vibrations contactor opened (2 Gn, 5...300 Hz) , shocks contactor closed (15 Gn for 11 ms) , shocks contactor opened (10 Gn for 11 ms)
Climatic withstand conforming to IEC 60947-1 Annex Q category D exposure to damp heat,  conforming to IACS E10 exposure to damp heat
Standards IEC 60335-1, EN/IEC 60947-5-1, CSA C22.2 No 14, UL 508, EN/IEC 60947-4-1
Height 77 mm
Permissible ambient air temperature around the device -40-70 °C at Uc, -5-60 °C
Operating altitude 3000 m without derating
Net weight 3.2 kg
Product certifications UKCA, RINA, GL, GOST, CCC, LROS (Lloyds register of shipping), CSA, BV, DNV, UL
IP degree of protection IP2X conforming to VDE 0106, IP2X conforming to IEC 60529
Depth 86 mm
Width 45 mm
Flame retardance V1 conforming to UL 94
Packing Units
Unit Type of Package 1 1
Number of Units in Package 1 1
Package 1 Height 4.700 cm
Package 1 Width 7.400 cm
Package 1 Length 8.800 cm
Package 1 Weight 334.000 g
Unit Type of Package 2 2
Number of Units in Package 2 24
Package 2 Height 15.000 cm
Package 2 Width 30.000 cm
Package 2 Length 40.000 cm
Package 2 Weight 8.586 kg